Data Center

Power & Cooling Converter

Convert between W, kW, VA, kVA, BTU/hr and tons of refrigeration, with power factor.

Power to convert

Relates real (W) and apparent (VA) power.

Why power and cooling share a calculator

Almost all the electrical power a server draws becomes heat, so the real power it consumes (watts) is also, to a close approximation, the cooling load you must remove. That's why this tool converts electrical and thermal units together — size the UPS and PDU from the power figures, and the CRAC/CRAH or mini-split from the BTU/hr and tons.

Real vs apparent power, and power factor

UPS and generator capacities are quoted in VA/kVA (apparent power); equipment draw is in W/kW (real power). They're linked by the power factor: W = VA × PF. Modern servers have PFC supplies with a power factor near 1.0, so VA ≈ W, but older or mixed loads run lower — size apparent power with the real PF or you'll overload the UPS. The conversions used here: 1 W = 3.412 BTU/hr, and 1 ton of refrigeration = 12,000 BTU/hr = 3,517 W.

These calculators run entirely in your browser — nothing you type is sent anywhere. Results are estimates for planning; validate against your vendor's documentation before you buy or deploy.